E084 Circulation pump fault

Medium severity WEC Series

What the control is telling you

Fault in the circulation pump during Install Check Mode. The pump should vibrate and make some noise when running from State 34.

Applies to: WEC600

Likely causes

  • Air in circulation pump line
  • Faulty circulation pump or harness
  • Faulty TDS sensor or harness

Test and repair steps

  1. If air is in the circulation pump line, reset the error and restart Install Check Mode.
  2. If the error returns, check whether the circulation pump runs properly from State 34 with some vibration and noise.
  3. If the pump is not running properly, replace the circulation pump or its harness.
  4. If the pump runs properly, replace the TDS sensor or its harness.

Other codes on the same units

  • E080 Right drain regeneration line opening
  • E081 Left product water solenoid valve opening
  • E082 Right product water solenoid valve opening
  • E083 CIP dosing pump fault
  • E090 - E100 Individual sensor or pump fault
  • E105 PCB fault
  • E106 PCB or harness fault
  • E107 PCB or harness fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.