E081 Left product water solenoid valve opening
What the control is telling you
Left product water solenoid valve opening fault. Check whether water flows to the drain when the faucet is opened.
Applies to: WEC600
Likely causes
- Faulty product water solenoid valve or harness
- Faulty flow sensor or harness
Test and repair steps
- Open the faucet and check whether water flows to the drain.
- If water flows to the drain, replace the corresponding drain line product water solenoid valve or its harness.
- If not, replace the flow sensor or its harness.
- Reset the error.
Other codes on the same units
- E077 Left drain regeneration line closed
- E078 Right drain regeneration line closed
- E079 Left drain regeneration line opening
- E080 Right drain regeneration line opening
- E082 Right product water solenoid valve opening
- E083 CIP dosing pump fault
- E084 Circulation pump fault
- E090 - E100 Individual sensor or pump fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.