E020 Bypass or pressure sensor error
What the control is telling you
Error may occur from a temporary water cut-off, or from a bypass valve or pressure sensor fault.
Applies to: WEC600
Likely causes
- Temporary water cut-off
- Inlet pressure outside allowable range
- Pressure sensor or harness faulty
- Bypass valve or harness faulty
Test and repair steps
- If E020 occurs again within 7 seconds after the unit enters standby, check the inlet water pressure is within the allowable range.
- If pressure is in range, replace the pressure sensor or its harness.
- Check whether the customer's house is supplied with water and whether water flows to the drain line when the faucet is opened.
- If water does not flow to the drain line, replace the bypass valve or its harness.
- Close the faucet and reset the error manually.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.