Navien · General

E010 High inlet water pressure

Medium severity WEC

What the control is telling you

Inlet water pressure is above the allowable limit or the pressure sensor reading is wrong.

Applies to: WEC600

Likely causes

  • Inlet pressure above 72 psi
  • Pressure sensor or harness faulty

Test and repair steps

  1. Check whether the house inlet pressure exceeds 72 psi.
  2. If it does, reduce inlet pressure to the allowable range using a pressure relief valve.
  3. If it does not, replace the pressure sensor or its harness.

Other codes on the same units

  • 130 Power board communication error
  • E001 Leak detected
  • E002 Drain line flow error
  • E003 Drain line flow error
  • E020 Bypass or pressure sensor error
  • E021 Regeneration line #1 open error (left)
  • E022 Regeneration line #2 open error (right)
  • E023 Bypass solenoid valve error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 59. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.