130 Power board communication error

High severity WEC

What the control is telling you

The main panel and the power board are not communicating.

Applies to: WEC600

Likely causes

  • Main panel or power board not connected properly

Test and repair steps

  1. Check the connection between the main panel and the power board; connect them if not connected.
  2. If connected, wait for automatic error reset or unplug the power cord and plug it back in.
  3. If the code returns, call an authorized service professional and open the bypass valve to use feedwater until the error is cleared.

Other codes on the same units

  • 119 Under frequency inverter
  • 120 AD offset error
  • 122 Heat sink sensor error
  • 123 Fan error
  • 124 Security-chip error
  • E001 Leak detected
  • E002 Drain line flow error
  • E003 Drain line flow error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 58. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.