Navien · General
E003 Drain line flow error
What the control is telling you
Water is not flowing correctly to a drain line during operation. Flowchart is shared with E002.
Applies to: WEC600
Likely causes
- House water supply not available
- Drain line regeneration solenoid valve or harness faulty
- Main solenoid valve or harness faulty
- Drain line flow switch or harness faulty
- Inlet water pressure outside allowable range
Test and repair steps
- Wait until water is supplied, and check whether the error resets automatically after 30 seconds.
- Check that the customer's house is supplied with water.
- Check that water is supplied to the drain line.
- If either drain line is not working, replace its regeneration solenoid valve or harness.
- If both drain lines are not working, replace the main solenoid valve or harness.
- If the error occurs again after replacing the main solenoid valve, replace the regeneration solenoid valve or harness.
- Check that inlet water pressure is within the allowable range.
- If the error occurs again, replace the drain line flow switch or harness.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 59. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.