Navien · General

122 Heat sink sensor error

Medium severity WEC

What the control is telling you

The heat sink sensor on the power board is faulty or not connected.

Applies to: WEC600

Likely causes

  • Heat sink sensor not connected

Test and repair steps

  1. Check the connection of the heat sink sensor; connect it if not connected.
  2. If connected, wait for automatic error reset or unplug the power cord and plug it back in.
  3. If the code returns, call an authorized service professional and open the bypass valve to use feedwater until the error is cleared.

Other codes on the same units

  • 116 Over voltage inverter
  • 117 Under voltage inverter
  • 118 Over frequency inverter
  • 119 Under frequency inverter
  • 120 AD offset error
  • 123 Fan error
  • 124 Security-chip error
  • 130 Power board communication error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.