Navien · General
E024 Regeneration line #1 blockage error (left)
What the control is telling you
Blockage in regeneration line #1 (left drain line).
Applies to: WEC600
Likely causes
- Blockage in left drain line
- Regeneration solenoid valve or harness faulty
- Bypass valve or harness faulty
- Inlet pressure outside allowable range
Test and repair steps
- Check whether water is supplied to the house and to the drain line.
- Enter Installer Setting Mode option 06 (Forced Flushing).
- Check that inlet water pressure is within the allowable range.
- If the blockage remains, replace the left drain line regeneration solenoid valve or its harness.
- If water does not flow to the drain line when the faucet is opened, replace the bypass valve or its harness.
- Close the faucet and reset the error manually.
Other codes on the same units
- E020 Bypass or pressure sensor error
- E021 Regeneration line #1 open error (left)
- E022 Regeneration line #2 open error (right)
- E023 Bypass solenoid valve error
- E025 Regeneration line #2 blockage error (right)
- E026 Drain line error (main solenoid path)
- E027 Drain line error (main solenoid path)
- E041 TDS sensor error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 61. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.