Navien · Air conditioner

E702 Outdoor unit to inverter driver communication failure

High severity Navien NAE

What the control is telling you

Mainboard cannot talk to the inverter board. Auto reset.

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Inverter malfunction
  • Mainboard malfunction
  • Communication connector problem

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check that the inverter has power.
  3. Check the connector between the inverter PCB and the mainboard. Replace the connector if needed.
  4. If the connections are good, replace the mainboard or contact a service center.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E506 Compressor suction temperature sensor (TS) open/short
  • E507 Condenser outlet temperature sensor (Tcond) open/short
  • E561 Discharge pressure sensor (PD) open/short
  • E562 Suction pressure sensor (PS) open/short
  • E801 Inverter trip: Communication error
  • E802 Inverter trip: Compressor current sensor error
  • E803 Inverter trip: DC link sensor error
  • E804 Inverter trip: PFCM current A error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 and 7.2.16, p.57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.