Navien · Air conditioner
E507 Condenser outlet temperature sensor (Tcond) open/short
What the control is telling you
The condenser outlet sensor reads open or shorted. Auto reset.
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Sensor defective, mispositioned or miswired
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check that the Tcond sensor sits in the right spot.
- Check its wiring against the wiring diagram.
- Measure its resistance and compare with the table. Nominal values by sensor temperature: -4 F 70.3 kohm, 32 F 27.7 kohm, 77 F 10.0 kohm, 104 F 5.81 kohm, 140 F 3.01 kohm, 212 F 0.98 kohm.
- Replace the sensor if resistance is out of range. If the sensor is good, replace the mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E210 High pressure switch (HPS) protection error
- E501 Outdoor temperature sensor (Ta) open/short
- E505 Compressor discharge temperature sensor (TD) open/short
- E506 Compressor suction temperature sensor (TS) open/short
- E561 Discharge pressure sensor (PD) open/short
- E562 Suction pressure sensor (PS) open/short
- E702 Outdoor unit to inverter driver communication failure
- E801 Inverter trip: Communication error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Sensor errors and 7.2, p.56. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.