Navien · Air conditioner

E561 Discharge pressure sensor (PD) open/short

Medium severity Navien NAE

What the control is telling you

A compressor pressure sensor reads open or shorted. Auto reset (display shows 561).

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Pressure sensor defective, mispositioned or miswired

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check the sensor position and wiring against the wiring diagram.
  3. Measure sensor resistance. It should be above 10 kohm.
  4. Replace the sensor if it is bad. If the sensor is good, replace the mainboard.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E501 Outdoor temperature sensor (Ta) open/short
  • E505 Compressor discharge temperature sensor (TD) open/short
  • E506 Compressor suction temperature sensor (TS) open/short
  • E507 Condenser outlet temperature sensor (Tcond) open/short
  • E562 Suction pressure sensor (PS) open/short
  • E702 Outdoor unit to inverter driver communication failure
  • E801 Inverter trip: Communication error
  • E802 Inverter trip: Compressor current sensor error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Sensor errors and 7.2.15, p.57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.