Navien · Air conditioner
E506 Compressor suction temperature sensor (TS) open/short
What the control is telling you
The compressor suction sensor reads open or shorted. Auto reset.
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Sensor defective, mispositioned or miswired
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check that the TS sensor sits in the right spot.
- Check its wiring against the wiring diagram.
- Measure its resistance and compare with the table. Nominal values by sensor temperature: -4 F 70.3 kohm, 32 F 27.7 kohm, 77 F 10.0 kohm, 104 F 5.81 kohm, 140 F 3.01 kohm, 212 F 0.98 kohm.
- Replace the sensor if resistance is out of range. If the sensor is good, replace the mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E209 Superheat protection error
- E210 High pressure switch (HPS) protection error
- E501 Outdoor temperature sensor (Ta) open/short
- E505 Compressor discharge temperature sensor (TD) open/short
- E507 Condenser outlet temperature sensor (Tcond) open/short
- E561 Discharge pressure sensor (PD) open/short
- E562 Suction pressure sensor (PS) open/short
- E702 Outdoor unit to inverter driver communication failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Sensor errors and 7.2, p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.