Navien · Air conditioner

E210 High pressure switch (HPS) protection error

High severity Navien NAE

What the control is telling you

Shown after alarm A260 has occurred three times. Manual reset needed (display shows 210). Errors E815 and E824 point back to this code.

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Inverter malfunction
  • Outdoor heat exchanger not working
  • High pressure switch bad
  • Refrigerant overcharge
  • High outdoor temperature

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Clean the outdoor air intake filter.
  3. Check that the outdoor fan runs.
  4. Check the high pressure switch and its sensor connector on the mainboard.
  5. Check the water spray.
  6. Check for refrigerant overcharge.
  7. If these check out, replace the inverter mainboard.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E206 Heatsink protection error
  • E207 Compressor temperature abnormal error
  • E208 Compressor suction temperature (TS) protection error
  • E209 Superheat protection error
  • E501 Outdoor temperature sensor (Ta) open/short
  • E505 Compressor discharge temperature sensor (TD) open/short
  • E506 Compressor suction temperature sensor (TS) open/short
  • E507 Condenser outlet temperature sensor (Tcond) open/short

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.10, p.52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.