Navien · Air conditioner
E206 Heatsink protection error
What the control is telling you
Shown after alarm A256 has occurred four times. Manual reset needed (display shows 206).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Outdoor fan airflow poor
- Dirty heat sink
- Inverter malfunction
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Clean the outdoor air intake filter with the unit off. Descale the condenser if scale has built up.
- Check that the outdoor fan runs. Check the fan connector on the mainboard.
- Look at the inverter heat sink condition.
- If all are good, replace the inverter mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E202 Low pressure (PS) protection error
- E203 Compressor discharge temperature (TD) protection error
- E204 Compression ratio (CR) protection error
- E205 Overcurrent (CUR) protection error
- E207 Compressor temperature abnormal error
- E208 Compressor suction temperature (TS) protection error
- E209 Superheat protection error
- E210 High pressure switch (HPS) protection error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.6, p.48. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.