E202 Low pressure (PS) protection error
What the control is telling you
Shown after alarm A252 has occurred four times. Manual reset needed (display shows 202).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Refrigerant low or leaking
- Refrigerant line blocked
- TXV malfunction
- Outdoor temperature too low
- Low airflow to the indoor unit
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check the indoor filter and indoor fan.
- Check the TXV.
- Check the system for refrigerant leaks.
- Check that the low pressure sensor is plugged in. If its resistance reads infinite, replace the sensor.
- If the sensor is fine, replace the mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- A872 Inverter trip alarm: Discharge FET error
- A873 Inverter trip alarm: Stator overheat (5 min)
- A874 Inverter trip alarm: PBA (power board) over temperature
- E201 High pressure (PD) protection error
- E203 Compressor discharge temperature (TD) protection error
- E204 Compression ratio (CR) protection error
- E205 Overcurrent (CUR) protection error
- E206 Heatsink protection error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.2, p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.