Navien · Air conditioner
E205 Overcurrent (CUR) protection error
What the control is telling you
Shown after alarm A255 has occurred four times. Compressor current is running too high. Manual reset needed (display shows 205).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Compressor current abnormally high
- Too much refrigerant
- Outdoor heat exchanger not working
- TXV malfunction
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check the water spray and the outdoor heat exchanger filter.
- Check the outdoor fan.
- Check the compressor and the TXV.
- Check for refrigerant overcharge.
- If these check out, replace the mainboard.
- If nozzles are clogged, replace them. Clean the intake filter and descale if needed. Check the fan connector on the mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E201 High pressure (PD) protection error
- E202 Low pressure (PS) protection error
- E203 Compressor discharge temperature (TD) protection error
- E204 Compression ratio (CR) protection error
- E206 Heatsink protection error
- E207 Compressor temperature abnormal error
- E208 Compressor suction temperature (TS) protection error
- E209 Superheat protection error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.5, p.47. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.