Navien · Air conditioner

E201 High pressure (PD) protection error

High severity Navien NAE

What the control is telling you

Shown after alarm A251 has occurred four times. The unit is locked out until you reset it by hand (display shows 201).

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Too much refrigerant, or outdoor heat exchanger not working
  • Outdoor temperature too high
  • Service valves closed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check the water spray and the pre-filter at the outdoor heat exchanger.
  3. Check that the outdoor fan runs.
  4. Check that the service valves are open.
  5. Check that the high pressure sensor is plugged in. If its resistance reads infinite, replace the sensor.
  6. If the sensor is fine, check the compressor and replace the mainboard if everything else checks out.
  7. Check that the water is spraying well. Look at the main water valve and the nozzles. If the nozzles are clogged, replace them or call a service center.
  8. Clean the outdoor air intake filter with the unit off. If scale has built up on the condenser, use an approved descaler.
  9. Check the outdoor fan. Look at the fan connector on the mainboard. Call a service center if the fan is bad.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • A871 Inverter trip alarm: Fan motor error (5 min)
  • A872 Inverter trip alarm: Discharge FET error
  • A873 Inverter trip alarm: Stator overheat (5 min)
  • A874 Inverter trip alarm: PBA (power board) over temperature
  • E202 Low pressure (PS) protection error
  • E203 Compressor discharge temperature (TD) protection error
  • E204 Compression ratio (CR) protection error
  • E205 Overcurrent (CUR) protection error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.1, p.43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.