Navien · Air conditioner
E204 Compression ratio (CR) protection error
What the control is telling you
Shown after alarm A254 has occurred four times. Manual reset needed (display shows 204).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Too much refrigerant
- Outdoor heat exchanger not working
- Outdoor temperature too high
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check the water spray and the pre-filter at the outdoor heat exchanger.
- Check the outdoor fan.
- Check the high and low pressure sensors.
- If these check out, replace the mainboard.
- If nozzles are clogged, contact a service center to replace them. Clean the intake filter and descale if needed. Check the fan connector on the mainboard.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- A874 Inverter trip alarm: PBA (power board) over temperature
- E201 High pressure (PD) protection error
- E202 Low pressure (PS) protection error
- E203 Compressor discharge temperature (TD) protection error
- E205 Overcurrent (CUR) protection error
- E206 Heatsink protection error
- E207 Compressor temperature abnormal error
- E208 Compressor suction temperature (TS) protection error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.4, p.46. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.