Navien · Air conditioner
E209 Superheat protection error
What the control is telling you
Shown after alarm A259 has occurred three times. Manual reset needed (display shows 209).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- Too much refrigerant
- Low or no airflow to the indoor unit
- TXV malfunction
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check the TXV.
- Check the indoor air filter and indoor fan.
- Check the low pressure sensor and TS sensor.
- Check for refrigerant overcharge.
- Inspect the indoor unit.
- If these check out, replace the mainboard or contact a service center.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E205 Overcurrent (CUR) protection error
- E206 Heatsink protection error
- E207 Compressor temperature abnormal error
- E208 Compressor suction temperature (TS) protection error
- E210 High pressure switch (HPS) protection error
- E501 Outdoor temperature sensor (Ta) open/short
- E505 Compressor discharge temperature sensor (TD) open/short
- E506 Compressor suction temperature sensor (TS) open/short
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.9, p.51. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.