Navien · Air conditioner

E801 Inverter trip: Communication error

High severity Navien NAE

What the control is telling you

Inverter trip error shown after alarm 851 occurred four times. Manual reset needed (display shows 801). Alarm shown first is 851.

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Electrical noise
  • Possible inverter damage

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. The system retries starting on its own. If it keeps happening, replace the inverter.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E507 Condenser outlet temperature sensor (Tcond) open/short
  • E561 Discharge pressure sensor (PD) open/short
  • E562 Suction pressure sensor (PS) open/short
  • E702 Outdoor unit to inverter driver communication failure
  • E802 Inverter trip: Compressor current sensor error
  • E803 Inverter trip: DC link sensor error
  • E804 Inverter trip: PFCM current A error
  • E805 Inverter trip: PFCM current B error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.18, p.58. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.