Carrier air conditioner error codes

61 codes (44 faults, 17 normal display and menu codes).

CodeMeaningSeverity / type
1Normal operation - 1 flashNormal status
1 longCapacity limited - one long flashNormal status
2Normal operation - 2 flashes (high stage)Normal status
4Four flashes - speed limiting, non-communicating thermostatNormal status
5Five flashes - brownout protection setting (24ANB/25HNB)Normal status
6Six flashes - brownout protection setting (24ANB/25HNB)Normal status
16Lost communication with user interfaceMedium
25Invalid model plug / inverter sizeHigh
31High pressure switch openHigh
32Low pressure tripMedium
33Lost inverter communicationMedium
45Outdoor control board failureHigh
46BrownoutMedium
47No 230 V at unitHigh
48Lost inverter communication - lockoutHigh
49Compressor over currentMedium
53Outdoor air temperature sensor faultMedium
54Suction temperature sensor faultMedium
55Outdoor coil temperature sensor faultMedium
56OAT / coil thermistor out of rangeMedium
57Suction pressure transducer faultMedium
59Discharge temperature high (event)Medium
61Fan inverter faultMedium
63Fan inverter current faultMedium
65DC bus voltage low - speed limitingMedium
66Outdoor fan dropped outMedium
67Stator heater faultMedium
6810-minute stage 2 warm-up delayLow
69Inverter / compressor internal faultHigh
71Compressor dropped outMedium
72Suction over temperature (event)Medium
73Contactor shortedHigh
74Discharge temperature lockoutHigh
75Maximum power mode - temperatureMedium
76Fan inverter lockoutHigh
77Maximum power mode - compressor currentMedium
79Compressor / inverter fault (failed start)Medium
81Low stage thermal lockoutHigh
82Suction over temperature lockoutHigh
83Low pressure lockout (4 hours)High
84High pressure lockout (4 hours)High
86Fan inverter current lockoutHigh
88Compressor / inverter lockoutHigh
91Inverter DC over voltage (event)Medium
92Inverter DC under voltage (event)Medium
95Compressor over current lockoutHigh
96DC under voltage lockoutHigh
97DC over voltage lockoutHigh
98High torque eventMedium
99High torque lockoutHigh
LD1MOC red LED LD1 (sizes 25-60)Normal status
LD5MOC green LED LD5 (sizes 25-60)Normal status
LED1MOC red LED1 (sizes 25-60)Normal status
LED3MOC amber LED3 (sizes 25-60)Normal status
LED200MOC red LED (sizes 13, 24B)Normal status
LED207MOC amber LED (sizes 13, 24B)Normal status
COMM LEDGreen COMM LED on - communicatingNormal status
Charging modeRefrigerant charging mode (25VNA8/24VNA9, communicating)Menu / mode display
CurtailmentUtility curtailment shown on user interfaceNormal status
ONAmber STATUS LED on solid - standbyNormal status
Status code recallStatus code recall mode (25VNA8/24VNA9)Menu / mode display

Models covered

24ACB724ANB12424ANB13624ANB14824ANB16024ANB72424ANB73624ANB74824ANB76024VNA924VNA91324VNA92424VNA92524VNA93624VNA93724VNA94824VNA94924VNA960CA17DLFULAQ24XAXDLFULAQ24XBXDLFULAQ36XBXDLFULAQ36XCXDLFULAQ48XCXDLFULAQ60XDX

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.