Carrier · Air conditioner
73 Contactor shorted
What the control is telling you
Amber STATUS light flashes 73: compressor voltage is present when there is no call for the compressor.
Applies to: Carrier 24ANB1/24ANB7 two-stage AC
Likely causes
- Contactor contacts welded or stuck closed
- Miswired control box
Test and repair steps
- Kill power and inspect the contactor contacts.
- Check the VS/L2 (or VR/VS) sensing wiring against the wiring label.
- Replace the contactor if stuck.
Models that show this code
8 models in Carrier 2-stage 24ANB/25HNB
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Table 18 Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.