Carrier · Air conditioner
16 Lost communication with user interface
What the control is telling you
Amber STATUS light flashes 16: the outdoor board no longer hears the Infinity user interface.
Applies to: Carrier 24ANB1/24ANB7 two-stage AC
Likely causes
- Loose or broken ABCD wiring
- Wiring fault at indoor unit or UI
- UI or indoor unit without power
Test and repair steps
- Check the A, B, C, D connections at the UI, indoor unit and outdoor board.
- Confirm 24 V between C and D at the outdoor unit.
- Look at the green COMM LED it should be on steady once messages are received.
- After 2 min without messages the board returns to standby.
Models that show this code
8 models in Carrier 2-stage 24ANB/25HNB
Other codes on the same units
- 1 Normal operation - 1 flash
- 2 Normal operation - 2 flashes (high stage)
- 5 Five flashes - brownout protection setting (24ANB/25HNB)
- 6 Six flashes - brownout protection setting (24ANB/25HNB)
- 25 Invalid model plug / inverter size
- 31 High pressure switch open
- 32 Low pressure trip
- 45 Outdoor control board failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Table 18 Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.