Carrier · Air conditioner

32 Low pressure trip

Medium severity Carrier Infinity 19VS 24VNA9Carrier 2-stage 24ANB/25HNB

What the control is telling you

Amber STATUS light flashes 32. Suction pressure dropped below the trip point (cooling about 33 psig or less, heating about 15 psig or less). After 3 trips it becomes code 83 (4-hour lockout). Type: Local; reset: 6 minutes.

Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)

Likely causes

  • See code 83 for causes

Test and repair steps

  1. Troubleshoot as code 83 (charge, airflow, closed valve, restriction, TXV).

Models that show this code

17 models in Carrier Infinity 19VS 24VNA9, Carrier 2-stage 24ANB/25HNB

24ANB12424ANB13624ANB14824ANB16024ANB72424ANB73624ANB74824ANB76024VNA924VNA91324VNA92424VNA92524VNA93624VNA93724VNA94824VNA94924VNA960

Other codes on the same units

  • 6 Six flashes - brownout protection setting (24ANB/25HNB)
  • 16 Lost communication with user interface
  • 25 Invalid model plug / inverter size
  • 31 High pressure switch open
  • 33 Lost inverter communication
  • 45 Outdoor control board failure
  • 46 Brownout
  • 47 No 230 V at unit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.19. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.