Carrier · Air conditioner
5 Five flashes - brownout protection setting (24ANB/25HNB)
What the display is showing
Five flashes and a pause on the amber STATUS LED report the state of the 230 V brownout protection after the installer toggles it (a last resort for very noisy power). The manual contradicts itself: Table 18 lists 5 flashes as protection disabled and 6 as active, while the written procedure says 5 = active (shipped state) and 6 = disabled. Confirm on the unit before relying on either reading. While the forced defrost short remains, OAT and OCT sensor faults are not cleared.
Applies to: Carrier 24ANB/25HNB two-stage units
What to do
- Brownout toggle (non-communicating) with power off, remove the OAT/OCT sensor connector and short the forced defrost pins, then power up.
- After about 3 seconds the setting toggles and the LED flashes the new state (5 or 6).
- Power down, refit the sensor connector and remove the short. Two toggles may be needed to reach the setting you want.
Models that show this code
8 models in Carrier 2-stage 24ANB/25HNB
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier residential A/C and heat pump service manual 24-25, Table 18 (brownout rows) and 230 V Brown-Out Protection Defeated, p.59-61. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.