Carrier · Air conditioner
82 Suction over temperature lockout
What the control is telling you
Amber STATUS light flashes 82. Suction temperature too high repeatedly (elevated from code 72). 4-hour lockout. Type: System malfunction; reset: 4 hours.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)
Likely causes
- Undercharged system
- Uninsulated vapor line
- Indoor TXV problem
Test and repair steps
- Cooling check subcooling in Charging Mode (or the subcooling chart on the control box door) and adjust charge (add charge if low).
- Insulate the vapor (suction) line.
- Troubleshoot the indoor TXV.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.23. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.