Carrier · Air conditioner

65 DC bus voltage low - speed limiting

Medium severity Carrier Infinity 19VS 24VNA9

What the control is telling you

Amber STATUS light flashes 65. Inverter DC voltage is low, so the unit limits speed. Type: Local; reset: Automatic.

Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)

Likely causes

  • Low supply voltage (under about 197 VAC)
  • Loose wire in the control box
  • Shutdown caused by another fault code
  • Inverter internal damage

Test and repair steps

  1. Measure supply voltage at the outdoor unit; if low, contact the utility.
  2. Check for loose wires in the outdoor control box.
  3. Check for other fault codes; if none and voltage is good, replace the inverter.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.21. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.