Bosch · Heat pump

AtL Ambient temperature limited

Low severity Bosch IDS LightBosch IDS Premium Connected

What the control is telling you

Operation is restricted because the outdoor temperature is outside the operating range.

Applies to: Bosch IDS Light BOVA15-24/36/60 and IDS Premium Connected BOVA36-20/60-20 R-454B heat pump outdoor units

Likely causes

  • Ambient outside 15-125 F in cooling or -4 to 86 F in heating
  • Thermostat O/B setting wrong
  • T4 sensor wiring or reading wrong

Test and repair steps

  1. Wait for the temperature to come back into range.
  2. Check the thermostat O/B setting for heating.
  3. Check the T4 resistance against the sensor table; reseat or replace T4 and restart.
  4. Check wiring against the diagram.

Models that show this code

5 models in Bosch IDS Light, Bosch IDS Premium Connected

BOVA15-24BOVA15-36BOVA15-60BOVA36-20BOVA60-20

Other codes on the same units

  • P11 High pressure protection (transducer)
  • P21 Low pressure protection
  • P31 Input over-current protection
  • P32 Compressor over-current protection
  • Check button Point check - read system values on the board display
  • EA Control and drive program mismatch
  • Force button Force button - forced cooling/heating (charge mode)
  • Force button 6 s Force button held 6 seconds - manual defrost test

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59; Bosch IDS Premium Connected installation BTC 762003301 D (02.2025), Fault Code Table 22 and 18.12 Error Code Troubleshooting. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.