Bosch · Heat pump

P31 Input over-current protection

High severity Bosch IDS LightBosch IDS Premium Connected

What the control is telling you

The outdoor unit's input current went too high.

Applies to: Bosch IDS Light BOVA15-24/36/60 and IDS Premium Connected BOVA36-20/60-20 R-454B heat pump outdoor units

Likely causes

  • Closed service valves
  • Loose compressor wiring
  • Shorted compressor
  • Board fault

Test and repair steps

  1. Warning: Switch off power and wait 3 minutes before measuring resistance or touching boards.
  2. Open valves; correct compressor wiring.
  3. Check compressor windings U/V/W and to ground.
  4. Compare input current with the point check value.
  5. Replace the board, then the compressor, if needed.

Models that show this code

5 models in Bosch IDS Light, Bosch IDS Premium Connected

BOVA15-24BOVA15-36BOVA15-60BOVA36-20BOVA60-20

Other codes on the same units

  • P1 High pressure protection
  • P4 High compressor discharge temperature
  • P5 Condenser coil temperature protection (cooling)
  • P11 High pressure protection (transducer)
  • P21 Low pressure protection
  • P32 Compressor over-current protection
  • AtL Ambient temperature limited
  • Check button Point check - read system values on the board display

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59; Bosch IDS Premium Connected installation BTC 762003301 D (02.2025), Fault Code Table 22 and 18.12 Error Code Troubleshooting. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.