Bosch · Heat pump
P1 High pressure protection
What the control is telling you
Head pressure is too high.
Applies to: Bosch IDS Light BOVA15-24/36/60 and IDS Premium Connected BOVA36-20/60-20 R-454B heat pump outdoor units
Likely causes
- High ambient (cooling over 125 F, heating over 86 F)
- Closed service valve or kinked line
- Overcharge
- Poor condenser airflow or failed fan
Test and repair steps
- Confirm the ambient temperature is in range.
- Open valves and clear line restrictions.
- Check charge, condenser airflow and fan motor.
- Replace the high pressure switch if it failed.
Models that show this code
5 models in Bosch IDS Light, Bosch IDS Premium Connected
Other codes on the same units
- H01 Drive chip communication fault
- LED1 green Green LED1 on - main board powered
- o37 Low refrigerant in heating
- P0 Control board / compressor IPM overheating
- P4 High compressor discharge temperature
- P5 Condenser coil temperature protection (cooling)
- P11 High pressure protection (transducer)
- P21 Low pressure protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59; Bosch IDS Premium Connected installation BTC 762003301 D (02.2025), Fault Code Table 22 and 18.12 Error Code Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.