Bosch · Heat pump
o37 Low refrigerant in heating
What the control is telling you
The unit detected too little refrigerant in heating mode.
Applies to: Bosch IDS Light BOVA15 (24/36/60) R-454B heat pump outdoor units
Likely causes
- Closed service valves
- Damaged refrigerant lines
- Failed transducer or T4/T5 sensor
- Undercharge
Test and repair steps
- Open the service valves.
- Check for damaged lines.
- Check the pressure transducer and T4/T5 sensors.
- Charge the system correctly.
Models that show this code
3 models in Bosch IDS Light
Other codes on the same units
- F41 High pressure sensor fault
- F42 Low pressure sensor fault
- H01 Drive chip communication fault
- LED1 green Green LED1 on - main board powered
- P0 Control board / compressor IPM overheating
- P1 High pressure protection
- P4 High compressor discharge temperature
- P5 Condenser coil temperature protection (cooling)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.