Bosch · Heat pump

Force button Force button - forced cooling/heating (charge mode)

Menu / mode display Bosch IDS 2.0Bosch IDS LightBosch IDS Premium Connected

What the display is showing

A short press of the FORCE button (SW1) while the unit is running in cooling puts it in forced operation at full capacity for checking charge. The unit only runs in this mode when the user starts it. The manual says a symbol appears on the display; the symbol could not be read from the text export. On IDS 2.0 the display then shows a bar symbol followed by the compressor frequency.

Applies to: BOVA IDS 2.0, IDS Premium Connected and IDS Light heat pumps

What to do

  1. Start the system in cooling mode
  2. Short press the FORCE button on the outdoor board
  3. Allow about 10 minutes to ramp up and 20 minutes to stabilise before taking charging readings

Models that show this code

7 models in Bosch IDS 2.0, Bosch IDS Light, Bosch IDS Premium Connected

BOVA-36HDN1-M20GBOVA-60HDN1-M20GBOVA15-24BOVA15-36BOVA15-60BOVA36-20BOVA60-20

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch IDS Premium Connected BTC 762003301 D (02.2025), 17.2 Subcooling Charging p.43-44; IDS 2.0 service Rev3 (07.2021), 10.2.2 Force Mode Operation p.32. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.