Bosch · Heat pump

Force button 6 s Force button held 6 seconds - manual defrost test

Menu / mode display Bosch IDS 2.0Bosch IDS LightBosch IDS Premium Connected

What the display is showing

Holding the FORCE button for 6 seconds on the outdoor board starts a forced defrost test. The unit has to be in a heating call and must already have run for 8 minutes or more. Defrost starts after about 40 seconds and the display shows dF. The test ends by itself and the display goes back to the running speed.

Applies to: BOVA IDS 2.0, IDS Premium Connected and IDS Light heat pumps

What to do

  1. Make sure there is a heat call and the unit has already run 8 minutes or more
  2. Press and hold the FORCE button for 6 seconds
  3. Wait about 40 seconds; the display shows dF
  4. For a second test wait 5 minutes and repeat

Models that show this code

7 models in Bosch IDS 2.0, Bosch IDS Light, Bosch IDS Premium Connected

BOVA-36HDN1-M20GBOVA-60HDN1-M20GBOVA15-24BOVA15-36BOVA15-60BOVA36-20BOVA60-20

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch IDS Premium Connected BTC 762003301 D (02.2025), 18.4 Defrost Description p.46; IDS Light BTC 762003308 D, Manual Defrost; IDS 2.0 service Rev3, 10.2.1 p.31. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.