Weil-McLain · Heat pump · Domestic hot water

System Type B, Application B1: DHW call priority behaviour

ECO HP

What happens, in order

  1. A DHW call is served until it is satisfied.
  2. If other zone calls are present, the DHW call is served for up to 1 hour.
  3. After 1 hour the system satisfies the zone calls.
  4. The heat pump target stays at T1STOPH (maximum temperature) until the DHW call is satisfied.

Timings and thresholds

ItemValue
DHW priority window when other zone calls are present1 hour

Applies to: System Type B, Application B1 with DHW priority

More Weil-McLain heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.