Weil-McLain · Heat pump · Domestic hot water
Application C3: DHW priority operation
What happens, in order
- A DHW call is received through the DHW-priority zone panel.
- The heat pump runs DHW priority until the DHW call is satisfied.
- Space heating is disabled during the DHW combi call.
- If a space heat call is present, space heating does not run until 1 hour after the DHW call starts.
Timings and thresholds
| Item | Value |
|---|---|
| Space heat start delay after DHW call initiated | 1 hour |
Applies to: System Type C, Application C3
More Weil-McLain heat pump sequences
- Configuration walk-through · Startup
- Heat pump downstream of boiler (non-condensing boiler) · Heating
- Heat pump upstream of boiler (condensing boiler) · Heating
- Application B1 DHW call and 1-hour limit · Domestic hot water
- Application C3 DHW priority sequence · Domestic hot water
- System Type B, Application B1: DHW call priority behaviour · Domestic hot water
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 54. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.