Weil-McLain · Heat pump · Domestic hot water

Application C3 DHW priority sequence

ECO HP

What happens, in order

  1. Heat pump runs DHW priority until the DHW call is satisfied.
  2. Space heating is disabled during a DHW combi call.
  3. If a space heat call is present, space heat waits until the DHW call has been running for the set time.

Timings and thresholds

ItemValue
Space heat start after DHW call initiated1 hour

Applies to: Application C3 multi-zone space heating with DHW as zone

More Weil-McLain heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 54. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.