Weil-McLain · Heat pump · Domestic hot water

Application B1 DHW call and 1-hour limit

ECO HP

What happens, in order

  1. A DHW call is served until it is satisfied.
  2. If other zone calls are present, the DHW call is served for up to 1 hour.
  3. After 1 hour the zone calls are satisfied, but the heat pump target stays at T1STOPH until the DHW call ends.

Timings and thresholds

ItemValue
DHW call with other zone calls present1 hour

Applies to: System Type B, Application B1 (boiler direct piped)

More Weil-McLain heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.