Trane · Furnace · Startup

Gas heating system start-up (manual gas valve procedure)

Gas Heating Systems

What happens, in order

  1. Set the thermostat to its lowest setting.
  2. Turn off all electrical power to the unit.
  3. Remove the front panel to reach the main gas valve.
  4. Move the gas valve toggle switch to OFF.
  5. Wait five minutes to clear any gas. If gas is smelled, stop and follow the gas-leak instructions, do not operate the unit.
  6. Move the gas valve toggle switch to ON.
  7. Reinstall the front panel and confirm all other panels are secured.
  8. Turn on electrical power to the unit.
  9. Set the thermostat to the desired temperature and the fan to AUTO. The unit then runs automatically.
  10. If the unit does not operate, follow the shutdown procedure to turn off gas and call a service technician or gas supplier.

Timings and thresholds

ItemValue
Wait after gas valve is turned off, before turning it back on5 minutes

Applies to: Gas heating system with automatic ignition (no standing pilot)

More Trane furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane gas heating system owner's information 32-5083-1C-EN, p. 2. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.