Trane · Furnace · Cooling
Cooling and heat pump calls on S8 furnace control
What happens, in order
- Thermostat R-Y1-G closes and 24 V arrives at Y1 and G
- 24 V goes to the outdoor unit through the thermostat wiring
- Indoor blower ramps to cooling airflow; display shows CP1 (S8B1/S8X1) or CL1 (S8X2)
- Second stage R-Y2 closes, 24 V goes to the outdoor unit, and the blower ramps to second-stage airflow (CP2 or CL2)
- Satisfied the outdoor unit stops and the blower stops unless a blower cool off delay is set in the menu; display returns to IDL
- On S8X2 with a heat pump, the factory Y1-O jumper must be removed for the right display and operation; with the jumper in, the display reads CL1
- On S8X2 for cooling, the jumper must stay in or the display reads HP1
Timings and thresholds
| Item | Value |
|---|---|
| EAC relay delay | about 2 s after blower starts |
| HUM relay delay | about 1 s after blower starts |
Codes you may see during this
Applies to: S8B1, S8X1 and S8X2 furnaces
Models
More Trane furnace sequences
- First-stage gas heating · Heating
- Heating call sequence of operation · Heating
- Heating sequence of operation · Heating
- Second-stage gas heating (S8X2 only) · Heating
- Cooling fan-off delay · Cooling
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, Sequence of Operation pp.59-61. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.