Trane · Furnace · Heating

Heating call sequence of operation

UH1DH1

What happens, in order

  1. On a thermostat call for heat, R and W close and the control runs its self-check.
  2. The control confirms the pressure switch is open and the limit switch(es) are closed, then starts the draft blower.
  3. When the draft blower reaches speed, the pressure switch closes and the ignitor warm-up begins.
  4. The ignitor heats, then the gas valve opens to feed gas to the burners.
  5. The flame sensor must prove ignition within the 4 second trial period.
  6. After ignition is proven, the indoor blower starts after the fan-on delay.
  7. When the thermostat is satisfied, the gas valve closes, flames go out and the draft blower stops.
  8. The indoor blower keeps running for the fan-off period, then the control shuts it off.

Timings and thresholds

ItemValue
Ignitor warm-up before gas valve opensabout 20 seconds
Flame sensor ignition trial period4 seconds
Indoor blower on delay, upflowabout 45 seconds after ignition
Indoor blower on delay, downflow10 seconds after ignition
Fan-off period (dip switch selectable)60, 100, 140 or 180 seconds; factory 100 seconds

Applies to: UH1 and DH1 gas furnaces

Models

AUH1B080A9421B

More Trane furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane 18-CD29D1-11 installer's guide, p. 40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.