Trane · Furnace · Heating

Second-stage gas heating (S8X2 only)

S8X2

What happens, in order

  1. Second stage cannot run without first stage
  2. Thermostat R-W2 closes and 24 V arrives at W2; display shows Ht2 then Xt2
  3. Control checks pressure switch 2 is open, then energizes the second-stage inducer relay and runs the inducer on high speed
  4. Second-stage gas valve relay closes and the blower ramps to second-stage heating speed
  5. Control watches pressure switch 2; if it has not closed in 45 seconds a PS2 open error is declared and the furnace stays on first stage
  6. After a PS2 failure the control waits 10 minutes and tries again; after the third failed try in the same call it stays on first stage until R-W2 opens
  7. W2 satisfied second-stage valve closes and the blower ramps down to first-stage speed
  8. W1 satisfied gas valve closes, inducer post-purge, blower off time

Timings and thresholds

ItemValue
Pressure switch 2 prove time45 s
Retry wait after PS2 failure10 min
Attempts per call3

Codes you may see during this

PS2 open error

Applies to: S8X2 two-stage furnaces

Models

S8X2

More Trane furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, Sequence of Operation pp.59-61. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.