Trane · Furnace · Heating

Heating sequence of operation

AUH1B

What happens, in order

  1. Thermostat calls for heat and R and W contacts close.
  2. Control runs its self-check and confirms pressure switch contacts are open and limit switch contacts are closed.
  3. Induced draft blower energizes.
  4. As the draft blower reaches speed, the pressure switch closes and the ignitor warm-up begins.
  5. Ignitor heats, then the gas valve opens to feed the burners.
  6. Flame sensor confirms ignition within a 4 second trial period.
  7. Fan-on delay times out and the indoor blower starts.
  8. On thermostat satisfied, gas valve closes, flame goes out and the draft blower stops.
  9. Indoor blower runs through the fan-off period, then the control shuts it off.

Timings and thresholds

ItemValue
Ignitor warm-up before gas valve opensapprox. 20 s
Flame sensor ignition trial4 s
Blower ON delay (upflow/horizontal)approx. 45 s
Blower ON delay (downflow)10 s
Fan-off period60, 100, 140 or 180 s (factory 100 s)

Codes you may see during this

2 Flashes 3 Flashes

Applies to: AUH1B furnaces

More Trane furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.