KeepRite · Furnace · Heating
Two-stage 95% furnace: low/high heat, staging and blower delays
What happens, in order
- Single-stage thermostat (TT switch off) runs low heat for the first 12 minutes of a cycle then moves to high heat
- Two-stage thermostat (SW1-1 TT switch ON): R-W1 gives low heat, R-W1 plus W2 gives high heat; W2 always forces high heat
- Low heat blower comes on at low-heat speed 45 s after the gas valve opens
- High heat blower comes on at high-heat speed 25 s after the gas valve opens; high-heat pressure switch must close and the high gas valve opens
- If the high-heat pressure switch does not close, the furnace stays at low heat for up to 2 minutes after ignition; if it still has not closed the gas valve shuts, the heat-off delay runs, and a new cycle starts if heat is still called
- Low to high inducer goes to high speed, the high pressure switch closes, the high gas valve opens and the blower moves to high-heat speed 5 s later
- High to low (two-stage thermostat only) high gas valve closes, inducer drops to low, blower moves to low-heat speed 5 s after W2 opens; with a single-stage thermostat it never steps down during the cycle
- Thermostat satisfied gas valve closes, inducer post-purges, then blower runs the heat-off delay
Timings and thresholds
| Item | Value |
|---|---|
| Low-heat blower-on delay | 45 s |
| High-heat blower-on delay | 25 s |
| Low to high blower change | 5 s |
| Single-stage thermostat low-heat time | 12 min |
| Max time on low heat waiting for high pressure switch | 2 min |
| Inducer post-purge | 15 s |
| Heat-off delay options | 90 / 120 / 150 / 180 s |
| Heat-off delay factory | 120 s |
Applies to: KeepRite / ICP (F-G)9MXT two-stage 95% furnace (KeepRite G9MXT)
Models
More KeepRite furnace sequences
- Modulating 95% furnace: ignition sequence and retries · Ignition
- Single- and two-stage 95% furnace: ignition sequence and retries · Ignition
- Modulating 95% furnace: adaptive heating, staging and blower delays · Heating
- Single-stage 95% furnace: heating cycle and blower delays · Heating
- Furnace blower with outdoor A/C: cooling, dehumidify and continuous fan · Cooling
- Furnace used with a heat pump (dual fuel blower timing) · Other
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: KeepRite/ICP (F-G)9MXT service manual 440 04 4321 10, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.