KeepRite · Furnace · Ignition
Single- and two-stage 95% furnace: ignition sequence and retries
What happens, in order
- Thermostat closes R-W (W1) to call for heat
- Control self-checks and confirms the pressure switches are open, then starts the inducer (high speed on the two-stage)
- When the low-heat pressure switch closes the 15 s prepurge starts and the 24 V humidifier terminal is powered (9MXE ignores the housing pressure switch until 1 minute after the gas valve closes)
- Hot surface igniter warms for 17 s
- Gas valve opens; flame proving starts 5 s later and lasts 2 s; igniter stays on until flame is sensed or the proving window starts
- Flame proven inducer drops to low speed on the two-stage unit, and the blower-on delay begins
- No flame in 2 s gas valve closes and the control repeats the sequence up to 3 more times before ignition lockout
- Lockout clears automatically after 3 hours, or by interrupting 115 V power or 24 V at the control (not at W, G or R)
- Flame seen when it should be off control locks out gas heating and runs the inducer (at high speed) until flame is gone
Timings and thresholds
| Item | Value |
|---|---|
| Prepurge | 15 s |
| Igniter warm-up | 17 s |
| Flame proving | 2 s (starts 5 s after gas valve opens) |
| Ignition trials | 4 total |
| Lockout auto-reset | 3 hours |
Applies to: KeepRite / ICP (F-G)9MXE single-stage 95% furnace (KeepRite G9MXE); KeepRite / ICP (F-G)9MXT two-stage 95% furnace (KeepRite G9MXT)
Models
More KeepRite furnace sequences
- Modulating 95% furnace: ignition sequence and retries · Ignition
- Modulating 95% furnace: adaptive heating, staging and blower delays · Heating
- Single-stage 95% furnace: heating cycle and blower delays · Heating
- Two-stage 95% furnace: low/high heat, staging and blower delays · Heating
- Furnace blower with outdoor A/C: cooling, dehumidify and continuous fan · Cooling
- Furnace used with a heat pump (dual fuel blower timing) · Other
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: KeepRite/ICP (F-G)9MXE service manual 440 04 4311 09, Sequence of Operation / KeepRite/ICP (F-G)9MXT service manual 440 04 4321 10, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.