KeepRite · Furnace · Other

Furnace used with a heat pump (dual fuel blower timing)

(F-G)9MXE9MXT9MAE

What happens, in order

  1. Control sees R-W with Y1 (or Y/Y2) and changes its blower timing so the duct air does not go cold during heat pump defrost
  2. Blower is brought on at the matching cooling or heat speed and stays on through prepurge, then shuts off 24 s (25 s on 9MAE after burners light) and comes back at heat speed
  3. W drops normal inducer post-purge runs; the blower follows any Y signal still present (cool speed with Y/Y2, low-cool with Y1); on the two-stage furnace it switches to cool speed after a 3 s delay
  4. If W, Y and G all drop together the blower runs the selected off-delay; if G stays on, the blower then moves to continuous fan speed

Timings and thresholds

ItemValue
Blower dropout in heat cycle24 s (9MXE, 9MXT); 25 s (9MAE)
Speed change after W drops (two-stage)3 s

Applies to: KeepRite / ICP (F-G)9MXE single-stage 95% furnace (KeepRite G9MXE); KeepRite / ICP (F-G)9MXT two-stage 95% furnace (KeepRite G9MXT); ICP (F-G)9MAE modulating 95% furnace

Models

9MXE9MXTG9MAE0601714A

More KeepRite furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP (F-G)9MXE service manual 440 04 4311 09, Sequence of Operation / KeepRite/ICP (F-G)9MXT service manual 440 04 4321 10, Sequence of Operation / ICP (F-G)9MAE service manual 440 04 4700 00, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.