Single-stage 95% furnace: heating cycle and blower delays

(F-G)9MXE

What happens, in order

  1. After flame is proven, blower starts at heat speed 25 s after the gas valve opens; air cleaner terminal comes on with the blower
  2. Thermostat satisfied gas valve closes and humidifier terminal drops
  3. Inducer runs a 15 s post-purge, then stops
  4. Blower keeps running for the heat-off delay (90, 120, 150 or 180 s), factory 120 s

Timings and thresholds

ItemValue
Blower-on delay25 s
Inducer post-purge15 s
Heat-off delay options90 / 120 / 150 / 180 s
Heat-off delay factory120 s

Applies to: KeepRite / ICP (F-G)9MXE single-stage 95% furnace (KeepRite G9MXE)

Models

9MXEG9MXE

More KeepRite furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP (F-G)9MXE service manual 440 04 4311 09, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.