KeepRite · Furnace · Heating
Modulating 95% furnace: adaptive heating, staging and blower delays
What happens, in order
- Starts in intermediate or maximum heat; after 45 s at intermediate heat it moves to minimum heat or to the calculated modulating rate
- First thermostat cycle after power-up runs at minimum heat; later cycles use a rate the control calculates from past heating run times
- If the calculated rate is 40 to 99 percent: 45 s at intermediate heat, then the calculated rate for up to 19 minutes, then maximum heat while heat is still called; if 100 percent it runs maximum heat only
- After a power interruption the stored rate is lost: 45 s intermediate heat, 19 minutes minimum heat, then maximum heat
- Switches SW1-2 (minimum heat only) and SW4-2 (intermediate heat only) force two-stage operation; if both are on it defaults to intermediate
- W2 always forces maximum heat; with a two-stage thermostat, opening W2 steps the inducer down gradually and the blower airflow changes after a 5 s delay once inducer speed is within 15 percent of the target
- Blower-on delay 45 s after gas opens at intermediate heat, 25 s at maximum heat; humidifier and air cleaner terminals stay on through the cycle
- Thermostat satisfied gas valve closes, inducer post-purges 15 s, blower runs the blower-off delay at minimum-heat airflow
- With a communicating control the furnace modulates over its full range (or within set min and max CFM), with the same start-up and shutdown steps
Timings and thresholds
| Item | Value |
|---|---|
| Intermediate heat start time | 45 s |
| Adaptive rate run time | up to 19 min |
| Blower-on delay, intermediate | 45 s |
| Blower-on delay, maximum | 25 s |
| Airflow change delay | 5 s |
| Inducer post-purge | 15 s |
| Blower-off delay options | 90 / 120 / 150 / 180 s |
| Blower-off delay factory | 120 s |
Applies to: ICP (F-G)9MAE modulating 95% furnace
Models
G9MAE0601714A
More KeepRite furnace sequences
- Modulating 95% furnace: ignition sequence and retries · Ignition
- Single- and two-stage 95% furnace: ignition sequence and retries · Ignition
- Single-stage 95% furnace: heating cycle and blower delays · Heating
- Two-stage 95% furnace: low/high heat, staging and blower delays · Heating
- Furnace blower with outdoor A/C: cooling, dehumidify and continuous fan · Cooling
- Furnace used with a heat pump (dual fuel blower timing) · Other
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ICP (F-G)9MAE service manual 440 04 4700 00, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.