KeepRite · Furnace · Ignition

Modulating 95% furnace: ignition sequence and retries

(F-G)9MAE

What happens, in order

  1. Thermostat closes R-W; control self-checks and confirms the low, medium and high pressure switches are open
  2. Inducer ramps up slowly; after the low and then the medium pressure switch close, the control records the inducer RPM to judge vent resistance, and a 25 s prepurge starts
  3. Hot surface igniter warms for 17 s
  4. Gas valve opens; flame proving starts 5 s later and lasts 2 s
  5. Flame proven inducer speed is trimmed slightly down if the cycle started at intermediate heat, or increased if it started at maximum heat
  6. No flame in 2 s gas valve closes and the control repeats the sequence up to 3 more times before ignition lockout; auto reset after 3 hours or by interrupting power
  7. Flame seen when it should be off control locks out gas heating and runs the inducer at full speed until flame is gone

Timings and thresholds

ItemValue
Prepurge25 s
Igniter warm-up17 s
Flame proving2 s
Ignition trials4 total
Lockout auto-reset3 hours

Applies to: ICP (F-G)9MAE modulating 95% furnace

Models

G9MAE0601714A

More KeepRite furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ICP (F-G)9MAE service manual 440 04 4700 00, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.