Navien · Heat pump troubleshooting
IoT module will not connect to Wi-Fi
What is going on
NaviLink does not show status. Wi-Fi LED stays solid red in operation mode, or the LED does not change in pairing mode.
Likely causes
- Weak Wi-Fi signal
- Router channel setting
- Authentication failed after connecting
- Wrong SSID or password
Check in this order
- Test the home Wi-Fi with another device first.
- Move the router and module closer. If the router cannot move, relocate the module on extension wire (up to 50 m of 24 AWG, indoors only; the module is not waterproof).
- Change the router channel.
- Check the WLAN security settings and that SSID and password are right.
- Factory reset from pairing mode, hold the button more than 10 seconds, then pair again.
Applies to: NAC-10SM IoT module on NAZ heat pump and NAE air conditioner
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAC-10SM IoT Module Operation & Installation Manual, Troubleshooting (NaviLink), p.12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.