Navien · Heat pump troubleshooting

IoT module dead (LED off)

Navien NAZ

What is going on

The Wi-Fi/IoT module on the heat pump shows no light.

Likely causes

  • Module connector not plugged in properly
  • Failed IoT module

Check in this order

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Reseat the IoT module connector.
  3. Still no LED replace the IoT module.

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 3.4 Troubleshooting, p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.